VantagePoint alerts

The following information describes the available VantagePoint alerts.

Table 1. VantagePoint alerts
VantagePoint alert nameEvent descriptionXylem recommended action
Blocked RelayThe relay should be open but a load is detected.Clear the alarm, apply the override, check for command success, then clear the override. If the alarm reappears, the relay is likely damaged.
GPS Location ChangedGPS location detected by module has changed from its installed location by more than the minimum distance threshold.This is likely an indication that the module was moved without updating the installed GPS location.
GPS PositionGPS hardware has failed to determine a location.This is likely due to environmental conditions such as being installed in a parking deck. Module will continue to search but may require a manual push of GPS location from a Hand Held Device.
High CurrentMeasured current is greater than the maximum current threshold.
High PowerMeasured power is greater than the maximum power threshold.
High TemperatureEnclosure temperature is greater than the maximum temperature rating of the product.This condition is outside of the product warranty.
Lamp FailureLamp has extinguished or failed to ignite when control module supplied power.This alarm likely indicates a light fixture issue and the bulb or LED arrays may need to be replaced.
Low CurrentMeasured current is less than the minimum current threshold.
Low PowerMeasured power is less than the minimum power threshold.
Low Power FactorAbsolute measured power factor is less than the minimum power factor threshold.
Memory ErrorA memory corruption has been detected and corrected.
Board FailureOccurs when a board-level failure is detected. For example, the light is OFF but the current level indicates it is ON.
Metrology FailureCommunication to the metrology circuit has failed.
Metrology ResetMetrology circuit indicates an unexpected reset but is still functioning.
Open CircuitThe relay should be closed but no load is detected.Clear the alarm, apply the override, check for command success, then clear the override. If the alarm reappears, the relay is likely damaged.
Over CurrentMeasured current exceeds hardware rating.This condition is outside the product warranty.
Over VoltageMeasured voltage exceeds hardware rating.This condition is outside the product warranty.
Power FailureUnit has detected a power failure condition.Check the power source.
Power SurgeMeasured line voltage is greater than the maximum voltage threshold.
Relay CorrectedOccurs when the relay state was corrected.
Self-Discovery FailureSelf-discovery has failed to identify the lamp.
Unchanged Light LevelPhotodiode has not detected a light level change in 26 hours.This is likely an indication of environmental interference keeping the photodiode from seeing light levels would change the light state from on to off or vice-versa.
Brownout DetectedMeasured line voltage is less than the minimum voltage threshold.
Communication FailTriggered when the application has not heard from the endpoint in more than 3 hours (configurable).
Cycling LampSet when the Lamp has extinguished twice with the relay closed.Monitor "Cycling Counter" for number of cycles as fixture is likely at End of Life.
DALI Driver FailureOccurs when there is Faulty communication between controller and lamp driver or DALI scene mismatch, including mismatch on DALI Scene information.This is likely a HW failure in the light fixture.
Daylight BurnerLight is incorrectly ON during daylight hours.Clear the alarm, apply the override, check for command success, then clear the override. If the alarm reappears then the relay is likely damaged.
Fixture Type ChangedOccurs when the light is connected to a different fixture type without first being set to inactive.
GPS Hardware FailureOccurs when communication with the GPS hardware has failed.