Aclara I-210+c alerts

These alerts, errors, and warnings apply to Aclara I-210+c meters with a FlexNet SmartPoint module.

This information is provided as a reference only.

Alarms may vary by device type. Please check the alarms for your meter's device type.

Table 1. Aclara I-210+c DT-105 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
Battery and Potential FailMetrology Battery and Potential FailureIndicates if battery failure or power outage has occurred.Metrology detected Battery and Potential fail.MetrologyConsult metrology manufacturer documentation.
BrownoutBrown OutThe voltage for the meter has dropped below the brownout threshold for a length of time.Each time the FlexNet module samples the voltage registers from the meter, the minimum voltage is compared to the “Brownout Voltage Threshold”. If the minimum voltage is lower than the threshold, the brownout bit is set. The brownout bit is cleared when the voltage average window resets. The voltage is sampled from the meter every 90 seconds and each quantity is updated. The minimum, maximum, and average voltages are reset every time the voltage average window resets. The voltage average window is programmable and can be set to 1 hour, 6 hours, 12 hours, and 24 hours. As an optional feature, the voltage averaging can be synchronized to be cleared on every scheduled meter read.Radio EndpointInvestigate reason for low voltage in field. Alarm reset at end of the VAW.
Click CountN/AClick Count. The meter is currently undergoing transformer breaker operations.A click event occurs where the power is lost long enough to detect the loss (6-240 line cycles meter configuration setting) but not for continued loss of power that crosses the Outage Time threshold where meter would then go into last gasp. The click counter field increments each time a short duration voltage outage occurs (the outage is greater than the click count threshold setting but shorter than the Outage Time Threshold setting). The counter goes to 255 before resetting back to zero.Radio EndpointInvestigate possible source of momentary outages in field.
Clock ErrorMetrology Clock ErrorClock error. The meter's clock failed.This event is set to indicate that meter lost its date and time. The Clock Error bit in Standard Status 1 in ST03. This flag is cleared when date and time is set in the meter.MetrologyConsult metrology manufacturer documentation.
Demand OverloadMetrology Demand OverloadDemand Overload. The demand value is higher than the programmed value.The demand value is higher than the programmed value.MetrologySelf-correcting when the demand drops below the set point.
EEPROMMetrology EEPROM ErrorIndicates if an EEPROM error has occurred.Metrology detected EEPROM error.MetrologyConsult metrology manufacturer documentation.
High Line Current Error The meter has high current.Metrology detected potential high line current event.MetrologyConsult metrology manufacturer documentation.
High TemperatureMetrology High TempDetermines if the meter has detected a high temperature condition.Metrology detected high temperature.MetrologyConsult metrology manufacturer documentation.
High Temperature / Hot SocketHigh Temperature DetectedHigh Temperature Alarm. The meter's internal temperature has exceeded the temperature threshold.The FlexNet microprocessor uses an embedded temperature sensor to measure the ambient temperature inside of the meter plastic enclosure. The temperature is sampled every 10 seconds. If the temperature read exceeds the “temperature alarm” threshold, six alarm messages with the temperature alarm bit set will be immediately transmitted. The temperature threshold defaults to 85C and is programmable to a range between 1 to 125 degrees C. The temperature alarm feature also includes hysteresis. After the temperature threshold is exceeded and temperature alarm messages are transmitted, the temperature must drop at least 15 degrees below the high temperature threshold before the temperature alarm function is re-enabled. This avoids having modules sending large amounts of temperature alarms when the ambient temperature inside of the meter is hovering around the high temperature threshold.Radio EndpointOn-site visit is required to investigate the meter socket and service.
High Temperature Auto OpenMetrology Disconnect Open IndicatorHigh Temperature Auto Open.The meter’s internal remote disconnect switch will be opened if the TAO temperature threshold is exceeded by either thermistor temperature. The TAO temperature threshold defaults to 0 (disabled).Radio EndpointOn-site visit is required to investigate the meter socket and service.
High VoltageOver VoltageHigh Voltage. The meter has detected that the voltage exceeds the high voltage threshold.The transmission mode for each alarm transmission depends on the SmartPoint module configuration. Typically high temperature alarm messages are transmitted on the priority channel.Radio EndpointInvestigate reason for high voltage in field. The alarm will reset when the voltage average window resets.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time synchronizes with the tower. Status.Radio EndpointNo user action is required. This is a status indication only.
Leading KVARhMetrology Leading KVARHLeading KVARH.Meter has detected a leading kVAr condition. The meter will display CA 040 000. Anytime leading kVAr is detected except that a value can be programmed, e.g. only set flag if in excess of X kVAr. Leading KVARH bit in Manufacturing Status1 of ST03.MetrologyInvestigate.
Loss of ProgramLoss of ProgramThe meter configuration process did not complete as expected.The Demand Overload, Leading kVArh, and Received kWh cautions remain set in the meter until cleared by a manual reset issued from the RNI.MetrologyInspect meter installation and connections.
Low Battery ErrorMetrology Low BatteryThe meter has lost voltage and a battery is not connected or has failed. This causes the meter clock to stop. This warning is expected on meters without a battery. Potential Fail.The meter's battery has low voltage. This will also appear if the battery is missing.MetrologyIf meter has a battery, schedule field visit for battery replacement.
Low Loss PotentialMetrology Low Loss PotentialLow Loss Potential. The meter is missing phase.The meter voltage is below the set point. Meter will set Er 000 002 on the display. Meter will set LOW_LOSS_POTENTIAL_FLAG in STD TBL 3 in the meter.MetrologySelf-correcting. Will reset if voltage goes back above set point. See manufacturer documentation.
Meter Chip ErrorMetrology Meter Chip ErrorIndicates if an error occurred in the meter chip.Metrology detected a meter chip error.MetrologyConsult metrology manufacturer documentation.
Metering ErrorMetrology Metering ErrorMetrology detected a metering error.Metrology detected a metering error.MetrologyConsult metrology manufacturer documentation.
Metering Error Metering error.Metrology detected a metering error.MetrologyInvestigate.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMetrology Meter UnprogrammedMeter Unprogrammed.The meter is not currently programmed. Meter will show CA 000 010 on the display. Meter will set the UNPROGRAMMED_FLAG in STD TBL 3 in the meter.MetrologyProgram meter.
NONVOL ErrorMetrology Non Volatile Memory ErrorNONVOL Error. The meter cannot access the EEPROM.The metrology cannot access the nonvolatile ram. Meter will show Er 000 200 on the display. Metrology will set NONVOL_MEM_FAILURE_FLAG in STD TBL 3 in the meter.MetrologyReplace meter.
Over Class AmpsOver CurrentOver Class Amps. Set when the current flow exceeds the rated class amps.Each time the FlexNet module samples the current level registers from the meter, the maximum current is compared to the “High Current Threshold”. If the maximum current is greater than the threshold, the over class amps bit is set. The overclass amps bit is cleared when the voltage average window resets.Radio EndpointInvestigate service. The alarm will reset when the voltage average window resets.
Power FailPower FailLast Gasp.Each time the FlexNet module detects that the power monitor signal is de-asserted, the module enters a low power state and enters a hold-off period equal to the number of seconds stored as the “Outage Time Threshold”. The Outage Time Threshold is programmable in eight second increments and can be configured from 8 to 120 seconds. While the FlexNet module is in its low power state it continues to monitor the status of both power monitor signals. If either power monitor signal is re-asserted while the module is still in the hold-off period, the FlexNet module exits the low power state and continues to operate normally. No power fail transmissions are sent in this case.Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestorePower FailPower Restore.Upon power-on-reset (POR), the FlexNet module waits until the power monitor signal is asserted. Once the power monitor signal is asserted, the FlexNet module enters a hold-off time equal to the number of seconds stored as the “Restoral Time Threshold”. The Restoral Time Threshold is configurable in eight second increments and can be configured from 8 to 120 seconds. Once the hold-off time is complete, the device sends five dithered power restore alarms. Once all five power restoral transmissions have been sent, the device sends an on-air meter reading message.Radio EndpointNo user action required. This is a status indication only.
Processor ResetsN/AProcessor Resets. The number of times the meter's processor has been reset.The processor resets field is a modulo-16 counter that increments each time the FlexNet microprocessor is reset. Seeing this field increase is not necessarily an indication of a problem since this field will increment each time the power fails for longer than the Outage Time Threshold. A high value in this field only indicates a potential problem when the unit has not also been reporting a high number of power failures.Radio EndpointMonitor for excessive resets.
Received KWHMetrology Received KWHReceived kWh.Energy has been detected flowing in the reverse direction (load to line). The Demand Overload, Leading kVArh, and Received kWh cautions remain set in the meter until cleared by a manual reset issued from the RNI.MetrologyInvestigate.
Reverse EnergyReverse EnergyReverse energy.Reverse power flow has been detected continuously for five minutes each time the FlexNet module samples the voltage registers from the meter (90-sec), the reverse current flag will be checked. The first sample time in which the FlexNet module detects a reverse flow bit an optional alarm message will be sent. As a backup, in case that transmission was not received, the reverse energy bit is set in each meter read message until the voltage average window (VAW) expires even if the reverse energy condition has already cleared. If the meter’s reverse energy indication spans multiple VAW timeouts, an optional reverse energy alarm once during each VAW.Radio EndpointInvestigate the reason for the alarm.
ROM FailureMetrology ROM ErrorROM Failure. The meter had a problem accessing its nonvolatile EEPROM.The meter cannot access the EEPROM.MetrologyReplace meter recommended by Aclara.
RX Calibration Errors/Receiver CalibrationN/ARX Calibration Errors/Receiver Calibration. The number of times the receiver could not calibrate.The endpoint or device's time synchronizes with the tower. Status.Radio EndpointThe alarm will be cleared automatically when a static setup message is sent.
Single Phase OutageSingle Phase FailSingle phase outage.For a meter that has multiple phase voltages, the module has the ability to detect and report single phase outages. A single phase outage is defined as one of the power monitor signals from the meter reading less than 96 volts. The single phase outage detection is an edge sensitive. This means that the device must have been operating normal power prior to a single phase dropping out in order for the device to enter the single phase outage alarm messaging sequence. When a single phase outage event occurs the module will schedule three alarm messages to be sent with the single phase fail bit set. The power fail bit will not be set in these messages.MetrologyThe alarm will auto resolve when the AC power is restored to this phase. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
System ErrorMetrology System ErrorSystem error.The meter detected an internal hardware failure. Meter will display. Er 000 020. The System Error is triggered when the meter detects a problem with its internal hardware, most likely the microprocessor. This is in the ST 3, Manufacturing Status 1 field. Measurement Error bit (AKA Voltage reference Error) bit in Standard Status 1 are reported as weekly alarm.MetrologyReplace meter.
TamperTamperWhen a single phase outage event occurs the module will schedule three alarm messages to be sent with the 12S single phase fail bit set. The power fail bit will not be set in these messages. When the module schedules the single phase power fail messages it does not enter a low power state as it does during power fail. The device should behave normally since it is still powered from the line.Each time the FlexNet module detects a de-asserted power monitor signal, the electronic tamper algorithm starts. The electronic tamper detection monitors a hardware vibration sensor to determine if the meter has been removed from the socket. If the meter was removed from the socket, the FlexNet module will immediately send up to five power fail transmissions with the tamper bit set.Radio EndpointDoublecheck if there was a work order for this time. If not, on-site visit is required to investigate the status of the meter.
TX Lock Errors/Synthesizer Lock FailuresN/ATX Lock Errors/Synthesizer Lock Failures. The number of times the transmitter could not lock to a frequency.The TX Lock errors field is a modulo-16 counter that increments each time the transmit synthesizer fails to lock. For a transmitter that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointThe alarm will be cleared automatically when a static setup message is sent.
Watchdog TimeoutMetrology Watchdog TimeoutIndicates if a watchdog timeout has occurred.Metrology detected Watchdog Timeout.MetrologyConsult metrology manufacturer documentation.
Table 2. Aclara I-210+c DT-20 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
Clock Error Meter
Configuration Error (Demand or TOU)Error 0x0040. Typically indicates an error with TOU or demand configuration. Meter
Demand OverloadWarning 0x2000 or C&I Meter Alarm Flag 14,2. The reported power exceeded the capabilities of the meter. Demand threshold overload-CA004000. Meter
High Temperature DetectedSet when the internal meter temperature exceeds the configured temperature threshold. Meter
Low Battery Voltage ElectricLow battery - CA 000001 Meter
Low Loss PotentialLow potential - CA 000400 Meter
Measurement Error Meter
Meter UnprogrammedMeter unprogrammed - CA000001 Meter
Over CurrentHigh current. Meter
Over Voltage Meter
Power Fail Meter
RAM Failed Meter
RAM Test Fail Meter
Reverse EnergyReverse power detected or an 'Aclara I-210+c' Received KWH or an 'Aclara kV2c' Received kWh - CA 400000. Meter
ROM Failed Meter
ROM Test Fail Meter
Single Phase Fail Meter
Tamper Meter
BrownoutBrown OutThe voltage for the meter has dropped below the brownout threshold for a length of time.Each time the FlexNet module samples the voltage registers from the meter, the minimum voltage is compared to the “Brownout Voltage Threshold”. If the minimum voltage is lower than the threshold, the brownout bit is set. The brownout bit is cleared when the voltage average window resets. The first sample time in which the FlexNet module reads a voltage that sets the brownout condition an optional alarm message is sent. As a backup, in case that transmission was not received, the brownout bit is set in each meter read message until the voltage average window expires even if the brownout line condition has already cleared.Radio EndpointInvestigate reason for low voltage in field. Alarm reset at end of the VAW.
Clock ErrorMetrology Clock ErrorClock error. The meter's clock failed.This event is set to indicate that meter lost its date and time. The Clock Error bit in Standard Status 1 in ST03. This flag is cleared when date and time is set in the meter.MetrologyConsult metrology manufacturer documentation.
Demand OverloadMetrology Demand OverloadDemand Overload. The demand value is higher than the programmed value.The demand value is higher than the programmed value.MetrologyReprogram metrology or replace meter.
High Line Current Error The meter has high current.Metrology detected potential high line current event.MetrologyConsult metrology manufacturer documentation.
High Temperature / Hot SocketHigh Temperature DetectedThe meter's internal temperature has exceeded the temperature threshold.The FlexNet microprocessor uses an embedded temperature sensor to measure the ambient temperature inside of the meter plastic enclosure. The temperature is sampled every 10 seconds. If the temperature read exceeds the High Temperature threshold, ten alarm messages with the high temperature alarm bit set are immediately transmitted.Radio EndpointOn-site visit is required to investigate the meter socket and service.
High VoltageOver VoltageHigh Voltage. The meter has detected that the voltage exceeds the high voltage threshold.Each time the SmartPoint module samples the voltage registers from the meter, the maximum voltage is compared to the High Voltage Threshold. If the maximum voltage is greater than the threshold, the over voltage bit is set. The over voltage bit is cleared when the voltage average window resets.Radio EndpointInvestigate reason for high voltage in field. The alarm will reset when the voltage average window resets.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time is not synchronized with the tower.Radio EndpointNo user action is required. This is a status indication only.
Low Battery ErrorMetrology Low BatteryThe meter has lost voltage and a battery is not connected or has failed. This causes the meter clock to stop. This warning is expected on meters without a battery. Potential Fail.The meter's battery has low voltage. This will also appear if the battery is missing.MetrologyIf meter has a battery, schedule field visit for battery replacement.
Low Loss PotentialMetrology Low Loss PotentialLow Loss Potential. The meter is missing phase.The meter voltage is below the set point. Meter will set Er 000 002 on the display. Meter will set LOW_LOSS_POTENTIAL_FLAG in STD TBL 3 in the meter.MetrologySelf-correcting. Will reset if voltage goes back above set point. See manufacturer documentation.
Measurement ErrorMetrology Measurement ErrorMeasurement error.Meter detected a bad voltage reference.MetrologySelf-correcting. Contact Sensus if the issue persists.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data. If the meter cannot be read the meter read failure flag will be set and sent to identify an issue with collecting the reading value. For example, a wheel is between digits 3 and 4 during the reading the radio cannot read the value.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMetrology Meter UnprogrammedMeter Unprogrammed. The meter is not programmed currently.The meter is not currently programmed. Meter will show CA 000 010 on the display. Meter will set the UNPROGRAMMED_FLAG in STD TBL 3 in the meter.MetrologyProgram meter.
NONVOL ErrorMetrology Non Volatile Memory ErrorNONVOL Error. The meter cannot access the EEPROM.The metrology cannot access the nonvolatile ram. Meter will show Er 000 200 on the display. Metrology will set NONVOL_MEM_FAILURE_FLAG in STD TBL 3 in the meter.MetrologyReplace meter.
Over Class AmpsOver CurrentOver Class Amps.Each time the FlexNet module samples the current level registers from the meter, the maximum current is compared to the “High Current Threshold”. If the maximum current is greater than the threshold, the over class amps bit is set. The overclass amps bit is cleared when the voltage average window resets. This alarm not supported by the i210+c.Radio EndpointOn-site visit is required to investigate the meter socket and service.
Power FailPower FailPower Fail. The meter does not have any AC power.Each time the FlexNet module detects that the power monitor signal is de-asserted, the module enters a low power state and enters a hold-off period equal to the number of seconds stored as the “Outage Time Threshold”. The Outage Time Threshold is programmable in eight second increments and can be configured from 8 to 120 seconds. While the FlexNet module is in its low power state it continues to monitor the status of both power monitor signals. If either power monitor signal is re-asserted while the module is still in the hold-off period, the FlexNet module exits the low power state and continues to operate normally. No power fail transmissions are sent in this case. If the module completes its programmed hold-off time and the power monitor signals from the meter are still de-asserted, the module will then write the time of last power fail to flash memory and send up to five power fail transmissions. The power fail transmissions are randomly dithered within a 584 second window following expiration of the power outage threshold. Once a sequence of power fail alarms is transmitted a new sequence will not be sent until power is restored for the proper restoral period.Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestorePower FailPower Restore. AC Power is detected after a power fail.Upon power-on-reset (POR), the FlexNet module waits until the power monitor signal is asserted. Once the power monitor signal is asserted, the FlexNet module enters a hold-off time equal to the number of seconds stored as the “Restoral Time Threshold”. The Restoral Time Threshold is configurable in eight second increments and can be configured from 8 to 120 seconds. Once the hold-off time is complete, the device sends a number of power restore alarms and a read message per the Power Restore Transmissions Table. The transmission mode for each transmission depends on the module configuration. Typically, power restore messages are transmitted on the priority channel.Radio EndpointNo user action required. This is a status indication only.
Reverse EnergyReverse EnergyReverse energy. Reverse power flow has been detected.Each time the FlexNet module samples the voltage registers from the meter (90-sec), the reverse current flag will be checked. If the bit is set, a corresponding reverse energy bit will be set in the on-air FlexNet message. The FlexNet module’s reverse energy bit is cleared when the voltage average window resets.Radio EndpointInvestigate the reason for the alarm.
ROM FailureMetrology ROM ErrorROM Failure. The meter had a problem accessing its nonvolatile EEPROM.The meter cannot access the EEPROM.MetrologyReplace meter.
Single Phase OutageSingle Phase FailSingle phase outage.For a meter that has multiple phase voltages, the module has the ability to detect and report single phase outages. A single phase outage is defined as one of the power monitor signals from the meter reading less than 96 volts. The single phase outage detection is an edge sensitive. This means that the device must have been operating normal power prior to a single phase dropping out in order for the device to enter the single phase outage alarm messaging sequence. When a single phase outage event occurs the module will schedule three alarm messages to be sent with the single phase fail bit set. The power fail bit will not be set in these messages.MetrologyThe alarm will auto resolve when the AC power is restored to this phase. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
TamperTamperTamper. The meter's orientation has been moved or the cover has been opened.Each time the FlexNet module detects a de-asserted power monitor signal, the electronic tamper algorithm starts. The electronic tamper detection monitors a hardware vibration sensor to determine if the meter has been removed from the socket. If the meter was removed from the socket, the FlexNet module will immediately send up to five power fail transmissions with the tamper bit set.Radio EndpointDoublecheck if there was a work order for this time. If not, on-site visit is required to investigate the status of the meter.