Honeywell A3 alerts

These alerts, errors, and warnings apply to the Honeywell A3 meter with a FlexNet SmartPoint module.

Alarms may vary by device type. Please check the alarms for your meter's device type.

Table 1. Honeywell A3 DT-110 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
BrownoutBrown OutThe voltage for the meter has dropped below the brownout threshold for a length of time.Each time the FlexNet module samples the voltage registers from the meter, the minimum voltage is compared to the “Brownout Voltage Threshold”. If the minimum voltage is lower than the threshold, the brownout bit is set. The brownout bit is cleared when the voltage average window resets. The first sample time in which the FlexNet module reads a voltage that sets the brownout condition an optional alarm message is sent. As a backup, in case that transmission was not received, the brownout bit is set in each meter read message until the voltage average window expires even if the brownout line condition has already cleared.Radio EndpointInvestigate reason for low voltage in field. Alarm reset at end of the VAW.
Click CountN/AThe number of times AC voltage gaps that do not result in a power fail alarm.A click event occurs where the power is lost long enough to detect the loss (6-240 line cycles meter configuration setting) but not for continued loss of power that crosses the Outage Time threshold where meter would then go into last gasp. The click counter field increments each time a short duration voltage outage occurs (the outage is greater than the click count threshold setting but shorter than the Outage Time Threshold setting). The counter goes to 255 before resetting back to zero.Radio EndpointInvestigate reason for momentary voltage issues.
Clock ErrorMetrology Clock ErrorClock error. The meter's clock failed.This event is set to indicate that meter lost its date and time. The Clock Error bit in Standard Status 1 in ST03. This flag is cleared when date and time is set in the meter.MetrologyConsult Honeywell documentation.
Configuration ErrorConfiguration ErrorThis indicates a problem with the meter’s metrology configuration or program. The meter can usually be reprogrammed using Elster Electricity meter support software to correct the errors.C1219 standard errorMetrologyReview and reconfigure metrology per manufacturer.
Demand OverloadMetrology Demand OverloadDemand Overload. The demand value is higher than the programmed value.The demand value is higher than the programmed value.MetrologyReprogram metrology or replace meter.
High Temperature / Hot SocketHigh Temperature DetectedHigh Temperature. The meter's internal temperature has exceeded the configured temperature threshold.The FlexNet microprocessor uses an embedded temperature sensor to measure the ambient temperature inside of the meter plastic enclosure. The temperature is sampled every 10 seconds. If the temperature read exceeds the High Temperature threshold, ten alarm messages with the high temperature alarm bit set are immediately transmitted. The high temperature threshold defaults to 85°C and is programmable. Configuring the threshold less than 70°C fixes the threshold to 85°C. The high temperature alarm feature also includes hysteresis. After the temperature threshold is exceeded and temperature alarm messages are transmitted, the temperature must drop at least 15 degrees below the temperature threshold before the high temperature alarm function is re-enabled. This avoids having SmartPoint modules send many high temperature alarms when the ambient temperature inside of the meter is hovering around the high temperature threshold. The transmission mode for each alarm transmission depends on the SmartPoint module configuration. Typically high temperature alarm messages are transmitted on the priority channel.Radio EndpointOn-site visit is required to investigate the meter socket and service.
High VoltageOver VoltageHigh Voltage. The meter has detected that the voltage exceeds the high voltage threshold.Each time the SmartPoint module samples the voltage registers from the meter, the maximum voltage is compared to the High Voltage Threshold. If the maximum voltage is greater than the threshold, the over voltage bit is set. The over voltage bit is cleared when the voltage average window resets. The first sample time the SmartPoint module detects an over voltage condition, an optional alarm message is sent if real time alarm for over voltage is enabled. As a backup, in case that transmission was not received, the over voltage bit is set in each meter read message until the voltage average window expires, even if the over voltage condition has already cleared.Radio EndpointOn-site visit is required to investigate the meter socket and service.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time is not synchronized with the tower.Radio EndpointNo user action is required. This is a status indication only.
Low Battery ErrorMetrology Low BatteryLow Battery Error.The meter's battery has low voltage. This will also appear if the battery is missing.MetrologyIf meter has a battery, schedule field visit for battery replacement.
Low Loss PotentialMetrology Low Loss PotentialLow Loss Potential. The meter is missing phase.Voltage on phase A has dropped below the programmable set point.MetrologySelf-correcting. Will reset if voltage goes back above set point. See manufacturer documentation.
Measurement ErrorMeasurement ErrorMeasurement error.Temporary issue measuring energy.MetrologySelf-correcting. Contact metrology manufacturer if the issue persists.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.Meter Read Failure (MRF) indications are set internally when any metrology I/O operation fails. A MRF failure is communicated to the RNI on the next supervisory transmit event when an MRF alarm is sent instead of a reading message.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMeter UnprogrammedMeter Unprogrammed. The meter is not programmed currently.C1219 standard errorMetrologyReprogram metrology or replace meter.
NONVOL ErrorMetrology Non Volatile Memory ErrorNONVOL Error. The meter cannot access the EEPROM.The metrology cannot access the nonvolatile ram. Meter will show Er 000 200 on the display. Metrology will set NONVOL_MEM_FAILURE_FLAG in STD TBL 3 in the meter.MetrologyReplace meter recommended by Aclara.
Over Class AmpsOver CurrentOver Class Amps. Set when the current flow exceeds the rated class amps.Each time the FlexNet module samples the current level registers from the meter, the maximum current is compared to the “High Current Threshold”. If the maximum current is greater than the threshold, the over class amps bit is set. The overclass amps bit is cleared when the voltage average window resets.Radio EndpointOn-site visit is required to investigate the meter socket and service.
Power FailPower FailThe meter has lost power.Each time the FlexNet module detects that the power monitor signal is de-asserted, the module enters a low power state and enters a hold-off period equal to the number of seconds stored as the “Outage Time Threshold”. The Outage Time Threshold is programmable in eight second increments and can be configured from 8 to 120 seconds. While the FlexNet module is in its low power state it continues to monitor the status of both power monitor signals. If either power monitor signal is re-asserted while the module is still in the hold-off period, the FlexNet module exits the low power state and continues to operate normally. No power fail transmissions are sent in this case.Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestoreN/A - Restore is marked as the end of the Power Fail eventPower Restore. AC power is detected for a longer period than the configured Restore Time threshold after a loss of power occurred.Upon power-on-reset (POR), the FlexNet module waits until the power monitor signal is asserted. Once the power monitor signal is asserted, the FlexNet module enters a hold-off time equal to the number of seconds stored as the “Restoral Time Threshold”. The Restoral Time Threshold is configurable in eight second increments and can be configured from 8 to 120 seconds.Radio EndpointNo user action required. This is a status indication only.
Processor ResetsN/AProcessor resets. The number of times the meter's processor has been reset.The processor resets field is a modulo-16 counter that increments each time the FlexNet microprocessor is reset. Seeing this field increase is not necessarily an indication of a problem since this field will increment each time the power fails for longer than the Outage Time Threshold. A high value in this field only indicates a potential problem when the unit has not also been reporting a high number of power failures.Radio EndpointMonitor for excessive resets.
RAM FailureRAM FailedRAM Failed. The RAM checksum test failed during bootup.The RAM checksum test failed during boot-up. Counter that increments once every time the microprocessor is reset. Cleared by a static setup message.MetrologyReplace meter.
Register Memory Error The meter had a problem reading internal register data.Reported by metrology.MetrologyInvestigate.
Reverse EnergyReverse EnergyReverse energy. Reverse power flow has been detected.Reverse power flow has been detected continuously for five minutes Each time the FlexNet module samples the voltage registers from the meter (90-sec), the reverse current flag will be checked. The first sample time in which the FlexNet module detects a reverse flow bit an optional alarm message will be sent. As a backup, in case that transmission was not received, the reverse energy bit is set in each meter read message until the voltage average window (VAW) expires even if the reverse energy condition has already cleared. If the meter’s reverse energy indication spans multiple VAW timeouts, an optional reverse energy alarm once during each VAW.Radio EndpointInvestigate the reason for the alarm.
ROM FailureMetrology ROM ErrorROM failure. The meter had a problem accessing its nonvolatile EEPROM.The meter cannot access the EEPROM.MetrologyReplace meter.
RX Calibration Errors/Receiver CalibrationN/ARX Calibration Errors/Receiver Calibration. The number of times the receiver could not calibrate.The RX Calibration errors field is a modulo-16 counter that increments each time the mPass receiver fails to calibrate. For a receiver that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointInvestigate the reason for the alarm.
Single Phase OutageSingle Phase FailSingle phase outage.For a meter that has multiple phase voltages, the module has the ability to detect and report single phase outages. A single phase outage is defined as one of the power monitor signals from the meter reading less than 96 volts. The single phase outage detection is an edge sensitive. This means that the device must have been operating normal power prior to a single phase dropping out in order for the device to enter the single phase outage alarm messaging sequence. When a single phase outage event occurs the module will schedule three alarm messages to be sent with the single phase fail bit set. The power fail bit will not be set in these messages.MetrologyThe alarm will auto resolve when the AC power is restored to this phase. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
TamperTamperTamper. The meter's orientation has been moved or the cover has been opened.Each time the FlexNet module detects a de-asserted power monitor signal, the electronic tamper algorithm starts. The electronic tamper detection monitors a hardware vibration sensor to determine if the meter has been removed from the socket. If the meter was removed from the socket, the FlexNet module will immediately send up to four power fail transmissions with the tamper bit set.Radio EndpointDoublecheck if there was a work order for this time. If not, on-site visit is required to investigate the status of the meter.
TX Lock Errors/Synthesizer Lock FailuresN/ATX Lock Errors/Synthesizer Lock Failures. The number of times the transmitter could not lock to a frequency.The TX Lock errors field is a modulo-16 counter that increments each time the transmit synthesizer fails to lock. For a transmitter that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointInvestigate the reason for the alarm.
Table 2. Honeywell A3 DT-49 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
BrownoutBrown OutThe voltage for the meter has dropped below the brownout threshold for a length of time.Each time the FlexNet module samples the voltage registers from the meter, the minimum voltage is compared to the “Brownout Voltage Threshold”. If the minimum voltage is lower than the threshold, the brownout bit is set. The brownout bit is cleared when the voltage average window resets. As stated above, the first sample time in which the FlexNet module reads a voltage that sets the brownout condition an optional alarm message is sent. As a backup, in case that transmission was not received, the brownout bit is set in each meter read message until the voltage average window expires even if the brownout line condition has already cleared.Radio EndpointInvestigate reason for low voltage in field. Alarm reset at end of the VAW.
Click CountN/AThe number of times AC voltage gaps that do not result in a power fail alarm.A click event occurs where the power is lost long enough to detect the loss (6-240 line cycles meter configuration setting) but not for continued loss of power that crosses the Outage Time threshold where meter would then go into last gasp. The click counter field increments each time a short duration voltage outage occurs (the outage is greater than the click count threshold setting but shorter than the Outage Time Threshold setting). The counter goes to 255 before resetting back to zero.Radio EndpointInvestigate reason for momentary voltage issues.
Clock ErrorMetrology Clock ErrorClock error. The meter's clock failed.This event is set to indicate that meter lost its date and time. The Clock Error bit in Standard Status 1 in ST03. This flag is cleared when date and time is set in the meter.MetrologyConsult Honeywell documentation.
Configuration ErrorConfiguration ErrorThis indicates a problem with the meter’s metrology configuration or program.C1219 standard errorMetrologyReview and reconfigure metrology per manufacturer.
Demand OverloadMetrology Demand OverloadDemand Overload. The demand value is higher than the programmed value.The demand value is higher than the programmed value.MetrologyReprogram metrology or replace meter.
High Temperature / Hot SocketHigh Temperature DetectedHigh Temperature. The meter's internal temperature has exceeded the temperature threshold.The FlexNet microprocessor uses an embedded temperature sensor to measure the ambient temperature inside of the meter plastic enclosure. The temperature is sampled every 10 seconds. If the temperature read exceeds the High Temperature threshold, ten alarm messages with the high temperature alarm bit set are immediately transmitted. The high temperature threshold defaults to 85°C and is programmable. Configuring the threshold less than 70°C fixes the threshold to 85°C. The high temperature alarm feature also includes hysteresis. After the temperature threshold is exceeded and temperature alarm messages are transmitted, the temperature must drop at least 15 degrees below the temperature threshold before the high temperature alarm function is re-enabled. This avoids having SmartPoint modules send many high temperature alarms when the ambient temperature inside of the meter is hovering around the high temperature threshold. The transmission mode for each alarm transmission depends on the SmartPoint module configuration. Typically high temperature alarm messages are transmitted on the priority channel.Radio EndpointOn-site visit is required to investigate the meter socket and service.
High VoltageOver VoltageHigh Voltage. The meter has detected that the voltage exceeds the high voltage threshold.Each time the SmartPoint module samples the voltage registers from the meter, the maximum voltage is compared to the High Voltage Threshold. If the maximum voltage is greater than the threshold, the over voltage bit is set. The over voltage bit is cleared when the voltage average window resets. The first sample time the SmartPoint module detects an over voltage condition, an optional alarm message is sent if real time alarm for over voltage is enabled. As a backup, in case that transmission was not received, the over voltage bit is set in each meter read message until the voltage average window expires, even if the over voltage condition has already cleared.Radio EndpointOn-site visit is required to investigate the meter socket and service.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time is not synchronized with the tower.Radio EndpointNo user action is required. This is a status indication only.
Low Battery ErrorMetrology Low BatteryLow Battery Error.The meter's battery has low voltage. This will also appear if the battery is missing.MetrologyIf meter has a battery, schedule field visit for battery replacement.
Low Loss PotentialMetrology Low Loss PotentialLow Loss Potential. The meter is missing phase.Voltage on phase A has dropped below the programmable set point.MetrologySelf-correcting. Will reset if voltage goes back above set point. See manufacturer documentation.
Measurement ErrorMetrology Measurement ErrorMeasurement error.Meter detected a bad voltage reference.MetrologySelf-correcting. Contact Sensus if the issue persists.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data. If the meter cannot be read the meter read failure flag will be set and sent to identify an issue with collecting the reading value. For example, a wheel is between digits 3 and 4 during the reading the radio cannot read the value.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMetrology Meter UnprogrammedMeter Unprogrammed. The meter is not programmed currently.Set to true when the meter is cold started. It is used to indicate that the meter needs to be programmed by the user.MetrologyProgram meter.
NONVOL ErrorMetrology Non Volatile Memory ErrorNONVOL Error. The meter cannot access the EEPROM.The metrology cannot access the nonvolatile ram. Meter will show Er 000 200 on the display. Metrology will set NONVOL_MEM_FAILURE_FLAG in STD TBL 3 in the meter.MetrologyReplace meter.
Over Class AmpsOver CurrentOver Class Amps. Set when the current flow exceeds the rated class amps.Each time the FlexNet module samples the current level registers from the meter, the maximum current is compared to the “High Current Threshold”. If the maximum current is greater than the threshold, the over class amps bit is set. The overclass amps bit is cleared when the voltage average window resets.Radio EndpointOn-site visit is required to investigate the meter socket and service.
Power FailPower FailPower Fail. The meter does not have any AC power.Each time the FlexNet module detects that the power monitor signal is de-asserted, the module enters a low power state and enters a hold-off period equal to the number of seconds stored as the “Outage Time Threshold”. The Outage Time Threshold is programmable in eight second increments and can be configured from 8 to 120 seconds. While the FlexNet module is in its low power state it continues to monitor the status of both power monitor signals. If either power monitor signal is re-asserted while the module is still in the hold-off period, the FlexNet module exits the low power state and continues to operate normally. No power fail transmissions are sent in this case. If the module completes its programmed hold-off time and the power monitor signals from the meter are still de-asserted, the module will then write the time of last power fail to flash memory and send up to five power fail transmissions. The power fail transmissions are randomly dithered within a 584 second window following expiration of the power outage threshold. Once a sequence of power fail alarms is transmitted a new sequence will not be sent until power is restored for the proper restoral period.Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestorePower FailPower Restore. AC Power is detected after a power fail.Upon power-on-reset (POR), the FlexNet module waits until the power monitor signal is asserted. Once the power monitor signal is asserted, the FlexNet module enters a hold-off time equal to the number of seconds stored as the “Restoral Time Threshold”. The Restoral Time Threshold is configurable in eight second increments and can be configured from 8 to 120 seconds. Once the hold-off time is complete, the device sends five dithered power restore alarms. Once all five power restoral transmissions have been sent, the device sends an on-air meter reading message.Radio EndpointNo user action required. This is a status indication only.
Processor ResetsN/AProcessor resets. The number of times the meter's processor has been reset.The processor resets field is a modulo-16 counter that increments each time the FlexNet microprocessor is reset. Seeing this field increase is not necessarily an indication of a problem since this field will increment each time the power fails for longer than the Outage Time Threshold. A high value in this field only indicates a potential problem when the unit has not also been reporting a high number of power failures.Radio EndpointMonitor for excessive resets.
RAM FailureMetrology RAM FailureRAM Failure. The metrology RAM checksum test failed during bootup.Indicates a memory addressing error reported by the metrology processor. C1219 ST3MetrologyReplace meter.
Reverse EnergyReverse EnergyReverse energy. Reverse power flow has been detected.Reverse power flow has been detected continuously for five minutes each time the FlexNet module samples the voltage registers from the meter (90-sec), the reverse current flag will be checked. The first sample time in which the FlexNet module detects a reverse flow bit an optional alarm message will be sent. As a backup, in case that transmission was not received, the reverse energy bit is set in each meter read message until the voltage average window (VAW) expires even if the reverse energy condition has already cleared. If the meter’s reverse energy indication spans multiple VAW timeouts, an optional reverse energy alarm once during each VAW.Radio EndpointInvestigate the reason for the alarm.
ROM FailureMetrology ROM ErrorROM failure. The meter had a problem accessing its nonvolatile EEPROM.The meter cannot access the EEPROM.MetrologyReplace meter.
RX Calibration Errors/Receiver CalibrationN/ARX Calibration Errors/Receiver Calibration. The number of times the receiver could not calibrate.The RX Calibration errors field is a modulo-16 counter that increments each time the mPass receiver fails to calibrate. For a receiver that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointInvestigate the reason for the alarm.
Self Check ErrorMetrology Register Check ErrorThe meter failed the self-check during a reboot.The meter failed to self-check during a reboot.MetrologySelf-correcting. Contact Sensus if the issue persists.
Single Phase OutageSingle Phase FailSingle phase outage.For a meter that has multiple phase voltages, the module has the ability to detect and report single phase outages. A single phase outage is defined as one of the power monitor signals from the meter reading less than 96 volts. The single phase outage detection is an edge sensitive. This means that the device must have been operating normal power prior to a single phase dropping out in order for the device to enter the single phase outage alarm messaging sequence. When a single phase outage event occurs the module will schedule three alarm messages to be sent with the single phase fail bit set. The power fail bit will not be set in these messages.MetrologyThe alarm will auto resolve when the AC power is restored to this phase. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
TamperTamperTamper. The meter's orientation has been moved or the cover has been opened.Each time the FlexNet module detects a de-asserted power monitor signal, the electronic tamper algorithm starts. The electronic tamper detection monitors a hardware vibration sensor to determine if the meter has been removed from the socket. If the meter was removed from the socket, the FlexNet module will immediately send up to four power fail transmissions with the tamper bit set.Radio EndpointDoublecheck if there was a work order for this time. If not, on-site visit is required to investigate the status of the meter.
TX Lock Errors/Synthesizer Lock FailuresN/ATX Lock Errors/Synthesizer Lock Failures. The number of times the transmitter could not lock to a frequency.The TX Lock errors field is a modulo-16 counter that increments each time the transmit synthesizer fails to lock. For a transmitter that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointInvestigate the reason for the alarm.
Table 3. Honeywell A3 DT-34 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
Click CountN/AClick Count. The meter is currently undergoing transformer breaker operations.A click event occurs where the power is lost long enough to detect the loss (6-240 line cycles meter configuration setting) but not for continued loss of power that crosses the Outage Time threshold where meter would then go into last gasp. The click counter field increments each time a short duration voltage outage occurs (the outage is greater than the click count threshold setting but shorter than the Outage Time Threshold setting). The counter goes to 255 before resetting back to zero.Radio EndpointInvestigate possible source of momentary outages in field. Change the voltage source to reduce transformer breaker operations.
Clock ErrorMetrology Clock ErrorClock error. The meter's clock failed.This event is set to indicate that meter lost its date and time. The Clock Error bit in Standard Status 1 in ST03. This flag is cleared when date and time is set in the meter.MetrologyConsult Honeywell documentation.
Configuration ErrorConfiguration ErrorThis indicates a problem with the meter’s metrology configuration or program. The meter can usually be reprogrammed using Elster Electricity meter support software to correct the errors. .C1219 standard errorMetrologyReview and reconfigure metrology per manufacturer.
Demand OverloadMetrology Demand OverloadDemand Overload. The demand value is higher than the programmed value.The demand value is higher than the programmed value.MetrologyReprogram metrology or replace meter.
High Temperature / Hot SocketHigh Temperature DetectedHigh Temperature. The meter's internal temperature has exceeded the temperature threshold.The FlexNet microprocessor uses an embedded temperature sensor to measure the ambient temperature inside of the meter plastic enclosure. The temperature is sampled every 10 seconds. If the temperature read exceeds the High Temperature threshold, ten alarm messages with the high temperature alarm bit set are immediately transmitted.Radio EndpointOn-site visit is required to investigate the meter socket and service.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time is not synchronized with the tower.Radio EndpointNo user action is required. This is a status indication only.
Low Battery ErrorMetrology Low BatteryLow Battery Error.The meter's battery has low voltage. This will also appear if the battery is missing.MetrologyIf meter has a battery, schedule field visit for battery replacement.
Low Loss PotentialMetrology Low Loss PotentialLow Loss Potential. The meter is missing phase.Voltage on phase A has dropped below the programmable set point.MetrologySelf-correcting. Will reset if voltage goes back above set point. See manufacturer documentation.
Measurement ErrorMetrology Measurement ErrorMeasurement error.Meter detected a bad voltage reference.MetrologySelf-correcting. Contact Sensus if the issue persists.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMetrology Meter UnprogrammedMeter Unprogrammed. The meter is not programmed currently.Set to true when the meter is cold started. It is used to indicate that the meter needs to be programmed by the user.MetrologyProgram meter.
NONVOL ErrorMetrology Non Volatile Memory ErrorNONVOL Error. The meter cannot access the EEPROM.The metrology cannot access the nonvolatile ram. Meter will show Er 000 200 on the display. Metrology will set NONVOL_MEM_FAILURE_FLAG in STD TBL 3 in the meter.MetrologyReplace meter.
Power FailPower FailPower Fail. The meter does not have any AC power.Each time the FlexNet module detects that the power monitor signal is de-asserted, the module enters a low power state and enters a hold-off period equal to the number of seconds stored as the “Outage Time Threshold”. The Outage Time Threshold is programmable in eight second increments and can be configured from 8 to 120 seconds. While the FlexNet module is in its low power state it continues to monitor the status of the power monitor signal. If the power monitor signal is re-asserted while the module is still in the hold-off period, the FlexNet module exits the low power state and continues to operate normally. No power fail transmissions are sent in this case. If the module completes its programmed hold-off time and the power monitor signal from the meter are still de-asserted, the module will then write the time of last power fail to flash memory and send up to five power fail transmissions. The number of power fail transmissions depends on the transmitter operational mode and whether or not priority alarms are enabled. The power fail transmissions are randomly dithered within a 240 second window following expiration of the power outage threshold. After the sequence of power fail alarms are transmitted, a new sequence will not be sent until power is restored for the proper restoral period.Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestorePower FailPower Restore. AC Power is detected after a power fail.Upon power-on-reset (POR), the FlexNet module waits until power monitor signal is asserted. Once the power monitor signal is asserted, the FlexNet module enters a hold-off time equal to the number of seconds stored as the “Restoral Time Threshold”. The Restoral Time Threshold is configurable in eight second increments and can be configured from 8 to 120 seconds. Once the hold-off time is complete, the device sends a six dithered power restoral transmissions. Once all five power restoral transmissions have been sent, the device sends an on-air meter read message. The transmission mode for each transmission depends on the module configuration. Typically, power restore messages are transmitted on the priority channel.Radio EndpointNo user action required. This is a status indication only.
Processor ResetsN/AProcessor resets. The number of times the meter's processor has been reset.The processor resets field is a modulo-16 counter that increments each time the FlexNet microprocessor is reset. Seeing this field increase is not necessarily an indication of a problem since this field will increment each time the power fails for longer than the Outage Time Threshold. A high value in this field only indicates a potential problem when the unit has not also been reporting a high number of power failures.Radio EndpointMonitor for excessive resets.
RAM FailureMetrology RAM FailureRAM Failure. The metrology RAM checksum test failed during bootup.Indicates a memory addressing error reported by the metrology processor. C1219 ST3MetrologyReplace meter.
ROM FailureMetrology ROM ErrorROM failure. The meter had a problem accessing its nonvolatile EEPROM.The meter cannot access the EEPROM.MetrologyReplace meter.
TamperTamperTamper. The meter's orientation has been moved or the cover has been opened.Each time the FlexNet module detects a de-asserted power monitor signal, the electronic tamper algorithm starts. The electronic tamper detection monitors a hardware vibration sensor to determine if the meter has been removed from the socket. If the meter was removed from the socket, the FlexNet module will immediately send up to five power fail transmissions with the tamper bit set.Radio EndpointDoublecheck if there was a work order for this time. If not, on-site visit is required to investigate the status of the meter.
TX Lock Errors/Synthesizer Lock FailuresN/ATX Lock Errors/Synthesizer Lock Failures. The number of times the transmitter could not lock to a frequency.The TX Lock errors field is a modulo-16 counter that increments each time the transmit synthesizer fails to lock. For a transmitter that is operating under normal operating temperatures, this field should never be non-zero.Radio EndpointThe alarm will be cleared automatically when a static setup message is sent.
Table 4. Honeywell A3 DT-5 alerts
Meter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
Configuration ErrorConfiguration ErrorThis indicates a problem with the meter’s metrology configuration or program.C1219 standard errorMetrologyReview and reconfigure metrology per manufacturer.
In-Time SyncTime AdjustedIn-Time Sync. The endpoint or device's time synchronizes with the tower.The endpoint or device's time is not synchronized with the tower.Radio EndpointNo user action is required. This is a status indication only.
Measurement ErrorMeasurement ErrorMeasurement error.Temporary issue measuring energy.MetrologySelf-correcting. Contact metrology manufacturer if the issue persists.
Meter Read FailureMeter Read FailureMeter Read Failure. The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data.The meter could not be read due to no response, bad CRC/Checksum/Parity, or invalid data. If the meter cannot be read the meter read failure flag will be set and sent to identify an issue with collecting the reading value. For example, a wheel is between digits 3 and 4 during the reading the radio cannot read the value.Radio EndpointSelf-resolving. Replace the meter if the alarm continues repeatedly.
Meter UnprogrammedMeter UnprogrammedMeter Unprogrammed. The meter is not programmed currently.C1219 standard errorMetrologyReprogram metrology or replace meter.
Power FailPower FailPower Fail. The meter does not have any AC power.The meter transmits 4 alarms unless power comes back during the transmission/dither period, or the meter does not have enough reserve capacitor charge to allow it (for example, there is a brief power restore not allowing sufficient charging time, followed by another power fail).Radio EndpointThe alarm will auto resolve when the AC power is restored. If the power has been restored but the alarm persists then an on-site visit is required to investigate the status of the meter.
Power RestoreN/A - Restore is marked as the end of the Power Fail eventPower Restore. AC power is detected for a longer period than the configured Restore Time threshold after a loss of power occurred.AC power is detected after a power fail.Radio EndpointNo action necessary.
RAM FailureRAM FailedRAM Failed. The RAM checksum test failed during bootup.RAM Error bit in Standard Status 1 is reported as an immediate alarm.MetrologyReplace meter.