Electronic Register+ alerts

The following information describes the alarms, errors, and warnings for the Electronic Register+.

Table 1. Electronic Register+ alerts
LCD CodeMeter event nameRNI event nameEvent descriptionEvent triggerEvent sourceXylem recommended action
b (also displays battery icon)Battery Beyond End of LifeBeyond End of LifeTriggers when the product has reached the end of the expected product life base on years.Triggers after 21 yrs from date of manufacture.Smart MeterInvestigate.
b (also displays battery icon)Battery Near End of LifeNear End of LifeTriggers when the product is near the end of the expected product life based on years.Triggers after 20.5 yrs from date of manufacture.Smart MeterInvestigate.
Config ErrorConfiguration ErrorFactory Seal is not set.Configuration error alarm becomes active when factory seal is not set. Alarm is checked once an hour.Smart MeterInvestigate.
LCustomer LeakContinuous FlowTriggers when the flow rate through the meter meets or exceeds the configured value for the configured period of time.Triggers when flow rate exceeds configured value for configured time period. The defaults for 5/8" are 0.25 GPM, 0.05 M3/HR, 2 CF/HR in 24hr period. The defaults for 3/4" are 0.5 GPM, 0.11 M3/HR, 4 CF/HR in 24hr period. The defaults for 1" are 0.75 GPM, 0.17 M3/HR, 6 CF/HR in 24hr period.Smart MeterInvestigate.
HHigh FlowHigh FlowTriggers when the flow rate though the meter meets or exceeds the set value for the set time. Could be caused by a broken pipe.Triggers when flow rate exceeds set value for set period. The defaults for 5/8" are 20 GPM, 4.5 M3/HR, 160 CF/HR in an hour. The defaults for 3/4" are 30 GPM, 6.8 M3/HR, 240 CF/HR in an hour. The defaults for 1" are 50 GPM, 11.4 M3/HR, 400 CF/HR in an hour.Smart MeterInvestigate.
b (also displays battery icon)Low Metrology Battery VoltsLow Metrology Battery VoltsTriggers when voltage supplied to the metrology is running low.Triggers when volts drops below 2.8V.Smart MeterInvestigate.
Magnetic TamperMagnetic TamperTriggered when an attempt to tamper with the meter through the use of a magnet is detected.Triggers when magnet is detected.Smart MeterInvestigate.
Non-Volatile Memory ErrorConfiguration Error"Non-Volatile Memory Error". NV memory checksum failed.NV memory checksum failed.Smart MeterInvestigate.
RebootMeter RebootMeter has rebooted.Meter has rebooted.Smart MeterInvestigate.
Register Removal TamperMeter Disconnect TamperTriggered when an attempt to remove the register is detected.Triggers when an attempt is made to remove the register is detected.Smart MeterInvestigate.
Reverse FlowReverse FlowTriggers an alert when there is a consistent reverse flow for a specified period of time.Triggers when flow is detected in opposite direction. The default flow rate for 5/8", 3/4" and 1" are 1 GPM, 0.22 M3/HR, 8 CF/HR over a minute.Smart MeterInvestigate.
Upgrade ModeUpgrade ModeSet if the unit is in a mode that is updating the firmware.Triggered by receipt of a command to start Firmware Update.Smart MeterInvestigate.