Cordonel alarms
The following describes the alarms, errors, and warnings for the Cordonel meter.
Meter event name | RNI event name | Event description | Event trigger | Event source | Xylem recommended action |
---|---|---|---|---|---|
Beyond End of Life | Beyond End of Life | Triggers when the product has reached the end of the expected product life base on years. | Triggers after 20 yrs from install or 21 yrs from date of manufacture. | Smart Meter | Plan scheduled maintenance. |
Configuration Error | Configuration Error | Factory Seal is not set. | Configuration error alarm becomes active when factory seal is not set. Alarm is checked once an hour. | Smart Meter | Investigate. |
Critical Hardware Warning | Critical Hardware Warning | There may be an issue with peripheral meter hardware, though core metrology functions are not impacted. | Meter fault is detected. | Smart Meter | Investigate. |
Customer Leak | Continuous Flow | Triggers when the flow rate through the meter meets or exceeds the configured value for the configured period of time. | User configurable thresholds, defaults and permitted ranges based on meter size. | Smart Meter | Investigate. |
Empty Pipe | Empty Pipe | Triggers when air is detected in the pipe and indicates there is no water in the flow tube. | Triggers when air is detected in the pipe and indicates there is no water in the flow tube. | Smart Meter | Investigate. |
High Flow | High Flow | Triggers when the flow rate though the meter meets or exceeds the set value for the set time. Could be caused by a broken pipe. | User configurable thresholds, defaults and permitted ranges based on meter size. | Smart Meter | Investigate. |
High Pressure Alarm | High Pressure | Triggers when pressure rises above the set threshold. | Triggers when pressure is above set threshold. The defaults are 200 PSIG, 13.8 bar, 1.38 MPa over 1 minute. | Smart Meter | Investigate. |
High Temperature Alarm | High Temperature | Triggers when the temperature rises above the set range. | Triggers when temperature is above the set temperature. The defaults are 80F, 27C over a minute. | Smart Meter | Investigate. |
Low Pressure Alarm | Low Pressure | Triggers when pressure drops below the set threshold. | Triggers when pressure falls below the set threshold. The defaults are 35 PSIG, 2.4 bar, 0.24 MPa over a minute duration. | Smart Meter | Investigate. |
Low Primary Battery Volts | Low Metrology Battery Volts | Triggers when voltage supplied to the metrology is running low. | Triggers when volts drops below 2.8V. | Smart Meter | Plan scheduled maintenance. |
Low Temperature Alarm | Low Temperature | Triggers when the temperature drops below the set range. | Triggers when temperature falls below the set temperature. The defaults are 35F, 2C over a minute. | Smart Meter | Investigate. |
Near End of Life | Near End of Life | Triggers when the product is near the end of the expected product life based on years. | Triggers after 19.5 yrs from install or 20.5 yrs from date of manufacture. | Smart Meter | Plan scheduled maintenance. |
Reboot | Meter Reboot | Meter has rebooted. | Meter has rebooted. | Smart Meter | Investigate. |
Reverse Flow | Reverse Flow | Triggers an alert when there is a consistent reverse flow for a specified period of time. | User configurable thresholds, defaults and permitted ranges based on meter size. | Smart Meter | Investigate. |
Upgrade Mode | Upgrade Mode | Set if the unit is in a mode that is updating the firmware. | Triggered by receipt of a command to start Firmware Update. | Smart Meter | Investigate. |