Smart Gateway configuration

FieldLogic Hub allows you to customize the configuration of your Smart Gateway.

The Smart Gateway has four types of configurations:

  • Communication configurations: Choose how the Smart Gateway communicates in the FlexNet network.
  • Battery monitor configurations: Choose settings that affect the battery life.
  • Digital input alarms: Alarms triggered by a change in the state of an attached digital input.
  • Sensor alarms: Alarms triggered by readings from a sensor attached to a 4-20 mA analog input.
Table 1. Communication configurations
NamePurposeOptions
Configuration nameEnter a clear, descriptive name for this product configuration.Type the desired name into the text box.
Network TypeChoose the type of network the SmartPoint is installed into.If the drop-down menu is enabled, use the menu to select the appropriate type of network.
Fixed-base Network IntegrationChoose whether there are FlexNet electric meters and/or FlexNet Remote Transceivers in the network.Check the boxes to enable the FlexNet electric meters, Remote Transceivers, or both. This configuration option affects the SNR, Sample Rate, Transmit Rate, and Transmit Mode. These settings will be automatically adjusted based on your selection, and displayed in a table below the check boxes.
Table 2. Battery Monitor configurations
NamePurposeOptions
Infrastructure TypeChoose whether the configuration is for water or gas infrastructure.If enabled, use the drop-down menu to select either Water or Gas.
Sample rateChoose how frequently samples will be taken.If enabled, use the drop-down menu to select one of the following options:
  • Once per 5 minutes
  • Once per 15 minutes
  • Once per hour (recommended if not using analog inputs)
  • Once per 6 hours
  • Once per 12 hours
  • Once per 24 hours (recommended if using analog inputs)
Transmit rateChoose how frequently the Battery Monitor transmits.If enabled, use the drop-down menu to choose one of the transmission rate options between 5 minutes and 3.5 days, or never. If using analog inputs, the recommended transmit rate is every 84 hours. If not using analog inputs, the recommended transmit rate is every 4 hours.
Table 3. Digital Inputs configurations
NamePurposeOptions
Digital Inputs Alarm PersistenceChoose how long digital input alarms remain stay set in RNI after the stop condition is reached. Use the Digital Input Stop Alarm setting to latch the alarm if desired.Use the drop-down menu to select one of the following options:
  • Immediate (recommended)
  • 1 week
  • 1 month
  • 35 days
Digital Input 1 or 2 Alarm EnabledChoose whether the digital input alarm is enabled.To enable Digital Input Alarm 1 or 2, check the box.
Digital Input Alarm TriggerIf Digital Input Alarm Enabled is selected, allows you to select whether the digital input alarm is triggered by an open or closed circuit.Use the drop-down menu to select Open or Closed or, if available, Disabled.
Digital Input Alarm LabelIf Digital Input Alarm Enabled is selected, allows you to select a label for the digital input alarm.Use the drop-down menu to select one of the following options:
  • Open
  • Close
  • On
  • Off
  • High
  • Low
  • Full
  • Empty
  • Normal
  • Alarm
Digital Input Start AlarmChoose how long the trigger condition must be present before the alarm triggers.Use the drop-down menu to select one of the following options:
  • Immediate
  • 10 ms
  • 250 ms
  • 500 ms
  • 1 sec
  • 5 sec
  • 1 min
  • 10 min
Digital Input Stop AlarmChoose how long the alarm is active after the alarm stop condition is reached.Use the drop-down menu to select one of the following options:
  • 1 min
  • 1 hour
  • 1 day
When setting up sensor configurations, pay attention to the sensor settling delay. The following diagram shows how various sensor settings determine how the Smart Gateway takes samples:

  1. Settling delay. The maximum settling delay is 1500 ms.
  2. Time between samples. The minimum time between samples is 1 ms, maximum is 5 ms.
  3. Power off delay. The maximum power off delay is 1500 ms.
  4. The sample readings are averaged, and that average is reported.
  5. Sample count. In this example, the sample count is 4. The maximum sample count is 8.
Table 4. Smart Gateway Sensor configurations
NamePurposeOptions
Configuration NameSet a customized name for the sensor configuration.Type the desired name into the text box.
Sensor measuresChoose what your attached sensor is measuring.Use the drop-down menu to select one of the following options:
  • Temperature. Units: Celsius, Fahrenheit.
  • Pressure. Units: PSIG, PSIA, BarG, BarA.
  • Level/Distance. Units: ft, in, m, mm.
  • Weight: lbs, kg.
  • pH. Units: SU.
  • Conductivity. Units: mS/cm.
  • Blue-Green Algae. Units: RFU, cells/mL.
  • Chlorophyll. Units: RFU, ug/L.
  • Dissolved Oxygen. Units: mg/L.
  • Turbidity. Units: NTU.
  • Total Chlorine. Units: mg/L.
  • Free Chlorine. Units: mg/L.
  • Hydrogen Sulfide. Units: PPM.
  • Other/Unitless. Units: Value.
UnitsChoose the desired units. This option affects the other available configuration options.Use the drop-down menu to choose the desired units. Options will vary based on what the sensor measures.
Sensor settling delayChoose how long the sensor will be powered on before a reading is taken.Type the desired time into the text box, in milliseconds. Recommended default value: 1500 ms.
Sensor power off delayChoose how long the sensor will be powered on after a reading is taken.Type the desired time into the text box, in milliseconds. Default value: 0.0 ms.
Sensor sample countChoose how many samples are taken per sampling. These samples are averaged to produce one reading.Type the desired number of sample counts into the text box.
Time between samplesChoose the amount of time between samples.Type the desired time into the text box, in milliseconds.
PrecisionChoose the number of decimal places used in readings.Use the up and down arrow buttons to select the desired number of decimal places.
Activation settingsChoose where mA values are set during activation.Use the drop-down menu to choose one of the following options:
  • Prompt for Field Calibration: Change the actual value being measured, and have the Smart Gateway read the corresponding mA values. Not used for water utilities.
  • Prompt for mA values during Activation: During activation, use the factory calibration to tell the Smart Gateway the range of the sensor and how to scale the mA values.
  • Set mA values in Hub: During configuration creation, use the factory calibration to tell the Smart Gateway the range of the sensor and how to scale the mA values.
4 ma (minimum value) readingChoose the sensor reading that corresponds to a minimum value reading for the Smart Gateway.Type the desired value into the text box. Units vary depending on what is being measured.
20 ma (maximum value) readingChoose the sensor reading that corresponds to a maximum value reading for the Smart Gateway.Type the desired value into the text box. Units vary depending on what is being measured.
Prompt for sensor manufacturerChoose whether you want to prompt the FieldLogic Tools user for the sensor manufacturer.To enable prompting the user, check the box.
Prompt for sensor modelChoose whether you want to prompt the FieldLogic Tools user for the sensor model.To enable prompting the user, check the box.
Prompt for serial number during activationChoose whether you want to prompt the FieldLogic Tools user for the serial number.To enable prompting the user, check the box.
Prompt for elevation during activationChoose whether you want to prompt the FieldLogic Tools user for the elevation.To enable prompting the user, check the box.
Sample rateChoose how frequently samples are taken. This setting affects battery life.Use the drop-down menu to select the sample frequency. The chosen sample rate automatically adjusts the transmit rate. The available sample rate/ transmit rate pairs are:
  • Sample once per 12 seconds/transmit once per 1 minute
  • Sample once per 20 seconds/transmit once per 1 minute
  • Sample once per 1 minute/transmit once per 5 minutes
  • Sample once per 5 minutes/transmit once per 15 minutes
  • Sample once per 15 minutes/transmit once per 1 hour
  • Sample once per 1 hour/transmit once per 4 hours
  • Sample once per 6 hours/transmit once per 24 hours
  • Sample once per 24 hours/transmit once per 84 hours
Transmit rateChoose how frequently samples are transmitted. This setting affects battery life.The transmit rate adjusts automatically based on the chosen sample rate.
Fault Detection: High Measured UnitVaries depending on the type of sensor. Choose whether the sensor activates the High Measured Unit alarm, and the activation conditions.To enable the High Measured Unit alarm, check the box. Type the desired alarm trigger temperature and number of sample readings into the text boxes.
Fault Detection: Low Measured UnitVaries depending on the type of sensor. Choose whether the sensor activates the Low Measured Unit alarm, and the activation conditions.To enable the Low Measured Unit alarm, check the box. Type the desired alarm trigger temperature and number of sample readings into the text boxes.
Fault Detection: Measured Unit Inside RangeVaries depending on the type of sensor. Choose whether the sensor activates the Measured Unit Inside Range alarm, and the activation conditions.To enable the Measured Unit Inside Range alarm, check the box. Type the desired alarm trigger temperatures and number of sample readings into the text boxes.
Fault Detection: Measured Unit Outside RangeVaries depending on the type of sensor. Choose whether the sensor activates the Measured Unit Outside Range alarm, and the activation conditions.To enable the Measured Unit Outside Range alarm, check the box. Type the desired alarm trigger temperatures and number of sample readings into the text boxes.