While the alarm bits are consistent across all Base Stations, support for and names of alarms vary by cabinet, transceiver, and power supply.
Base Station enclosure type | "base_station_type" configuration parameter | Bit 1 | Bit 2 | Bit 3 | Bit 4 | Bit 5 | Bit 6 | Bit 7 | Bit 8 |
---|---|---|---|---|---|---|---|---|---|
M400D/M400DS Indoor with Victron Charger | 2 or 3 | Door Open - Indoor | No | No | Fuse Fail | AC Power Fail or Charger Fail | No | Low Battery | No |
M400D/M400DS Indoor with GE/Lineage Supply | 6 | Door Open - Indoor | No | No | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | No |
M4x0D/M4x0DS Outdoor | 6 | Door Open - Outdoor | Over Temperature Thermostat | Under Temperature Thermostat | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | Environmental Control Fault |
M400B/M400B2/M420B Outdoor Model with Alpha Power Supplies | 8 | Door Open - Outdoor | Over Temperature Thermostat | Under Temperature Thermostat | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | No |
Metro Model with GE/ Lineage Power Supply | 6 | Door Open - Outdoor | Over Temperature Thermostat | Under Temperature Thermostat | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | Environmental Control Fault |
R100NA Collector | 10 | Door Open | No | No | No | Power Fail | No | Low Battery | No |
Indoor S&D Models with Fuse Panel | 2 or 3 | Door Open - Indoor | No | No | Fuse Fail | AC Power Fail or Charger Fail | No | Low Battery | No |
Indoor T&Q Models with Argus/Alpha Supplies and Lithium Battery Sets | 4 | Door Open - Indoor | No | No | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | No |
Legacy Indoor S Models w/o Fuse Panel - obsolete | 0 | Door Open - Indoor, if equipped with Kit | No | No | No | AC Power Fail or Charger Fail, if equipped with Kit | No | Low Battery | No |
Legacy Alabama Power Co Outdoor Custom Minis, equipped with NewMar Supplies | 5 | Door Open - Outdoor | No | No | No | AC Power Fail or Charger Fail | No | Low Battery | No |
Outdoor Argus/Alpha Standard TE17 with Argus/Alpha Supplies | 1 | Door Open - Outdoor | Over Temperature Thermostat | Under Temperature Thermostat | Rectifier Major | AC Power Fail or Hi/Low | Rectifier Minor | Low Battery | Environmental Control Fault |
S1600E | 9 | Intrusion Alarm | No | No | Fuse Alarm | AC Power High/Low alarm or Fail | No | Low Battery | No |
R100E | 10 | Intrusion Alarm | No | No | No | AC Power Alarm | No | Low Battery | No |